Core
Made of high-quality cold-rolled grain-oriented silicon steel sheets.
Often adopts a 45° full mitered joint to allow magnetic flux to pass along the joint direction, effectively reducing no-load loss, no-load current, and core noise.
Core columns are usually bound with Class F non-woven tape and encapsulated with epoxy resin.
Performance Features
product details
Enclosure & Protection
Enclosure
Supports the core and windings while providing protection.
Made of high-quality steel plates with varying protection levels
IP00 (no protection)
IP20 (prevents solid objects >12mm)
IP23 (protects against dripping water)
Materials
cold-rolled steel, stainless steel, etc.
Protection Function
Dry-type transformers effectively block external contaminants such as dust and moisture, protecting internal components to ensure stable operation in various environments.
Temperature Control System
Equipped with an intelligent temperature monitoring system.
Automatically detects and displays winding temperatures.
Controls fan start/stop, alarms, and trip functions.
Temperature relays trigger alerts if overheating occurs.
Cooling Methods
● Natural Air Cooling (AN)
Operates at rated capacity continuously via natural convection.Suitable for stable loads and moderate environments.
● Forced Air Cooling (AF)
Uses fans to enhance cooling, increasing capacity by 50%.
Performance Characteristics
▪ No flammable resin or oil, reducing fire risk.
▪ Self-extinguishing, minimal smoke, and no toxic emissions.
Oil-free, eliminating leakage and pollution risks.
No oil checks or circulation, reducing upkeep costs.Equipped with protective enclosures and temperature control devices, we support air cooling, intelligent thermal protection, and real-time monitoring, further reducing maintenance efforts.
Strong short-circuit and thermal shock resistance.
Minimal partial discharge, high lightning impulse resistance.High thermal class (e.g., Class H: 180°C–220°C).
Low loss, low noise, and high operational efficiency.
Moisture-resistant, suitable for humid/salty conditions.
Compact and lightweight, they are easy to install and transport, and can be installed near the load center without requiring a special foundation,reducing installation time and costs.
Technical Parameters
| Voltage Ratings | 10kV, 20kV, 35kV, etc. |
| Capacity Range | 30kVA–20,000kVA (e.g., SCB-11—1250kVA/10kV, SG12 series 100–2500kVA). |
| Frequency | 50/60Hz. |
| Withstand Voltage | Typically 20,000V/min (tested with YZ1802 withstand voltage tester, 20mA). |
| Insulation Class | B, F, H, C (materials fiberglass-reinforced resin, NOMEX paper, etc.). Customizable. |
| Insulation Resistance | ≥2MΩ (tested with ZC25B-4 megohmmeter, <1000V). |
| Connection Types | Y/Y, Δ/Y0, Yo/Δ, autotransformer (optional). |
| Winding Temperature Rise | e.g., 100K. |
| Cooling Modes | AN (natural) or AF (forced air). |